Jiangsu Acrel Electrical Manufacturing CO.,LTD

Tel:+86-18761593924

E-Mail:lukas.lu@email.acrel.cn

AMC72L-E4/KC Three phase AC Multi-function Panel Energy Meter

AMC72L-E4/KC Three phase AC Multi-function Panel Energy Meter

AMC series meters adopt AC sampling technology, which can measure the current ,voltage,power, power factor and electric energy parameters in the power grid separately.

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Description
Major Characteristics
  • Voltage Rating:AC 100V,400V
  • Current Rating: AC 1A,5A
  • Pulse constant: 10000,40000,160000 imp/kWh
  • Switching input:2 channels or 4 channels passive contact input mode;Switching output:Output mode:2 channel relay NO contact output
  • Analog output:Contact capacity: 3A/30V DC, 3A/250V AC0~5V,0~20mA,4~20mA programmable
  • Frequency:0.05Hz,current,voltage:class 0.2, reactive;power:class 1.0,reactive energy:class 1.0,other:class 0.5,2~31st harmonic :±1%
  • Auxiliary power supply:AC/DC 85~265V
  • RS485/Modbus
Panel Features
 
 
 

 

Wiring

 

Installation
 
 
Network Structure

 

Installation On-Site

 

 

  •  
Related Products
  • PZ72L-E4 Three phase Energy meter
  • ADF400L-EY Multi Channel Prepaid Energy Meter
  • AMC96L-E4/KC Three Phase AC Multi-function Panel Energy Meter
  • AWT100-4G Wireless Communication Terminal 
  •  
  •  
  •  
Data Sheet
Function Ocerview

 

Function

Description&Value

Measurement

Three-phase AC kWh, kVarh, Active Power, Reactive Power, Forward&Reverse Power, Current, Voltage, Zero Sequence Voltage, Zero sequence Current, Voltage-phase Angle, Voltage&Current Unbalance, Power Factor,Harmonic, Frequency

Display

LCD display

Communication

(Optional)

RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity)

Baud Rate 1200~38400 bps etc.

Alarm Output

(Optional)

1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC,

Used for high,low,unbalance alarm etc.

Analog Output

(Optional)

1~5V DC or 4~20mA DC

DI/DO Switching

(Optional)

DI (Digital input): 2-channel or 4-channel dry contact digital input with built in power supply

DO (Digital output): 2-channel digital output with NO relay contact. Capacity: 3A/30V DC,3A/250V AC

 

Main Parameters

 

Parameter

Description&Value

Input

Rated Voltage

AC Voltage Input: 400V AC L-L (via direct connetion); 100V AC L-L (via -/100V AC PTs)

Rated Current 

AC Current Input: 5A AC or 1A AC (via -/5A AC or -/1A AC CTs)

Overload

Current&Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second

Frequency

45~65Hz

Power Consumption

Power consumption of each current&voltage input circuit is less than 0.5VA

Measuring Accuracy

Voltage

0.2%

Current

0.2%

Active Power

0.5%

Reactive Power

1.0%

kWh

0.5%

kVarh

1.0%

Frequency

±0.05Hz

Harmonic

±1%

Power Supply

Voltage Range

 85-265V AC/DC; 24V or 48V DC (±20%)

Power Consumption

≤10VA

Insulation resistance

≥ 100MΩ

Power frequency withstand voltage

Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min;

Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min;

Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min;

 

Environement

 

Condition

Description&Value

Temperature

Operation: -25℃~+65℃; Storage: -40°C ~+80°C

Humidity

≤95%RH,no condensation,without corrosive gas

Altitude

≤ 2500m

CONTACT US