Jiangsu Acrel Electrical Manufacturing CO.,LTD

Tel:+86-18761593924

E-Mail:lukas.lu@email.acrel.cn

AM5SE-IS Anti-Islanding Monitoring Relay

AM5SE-IS Anti-Islanding Monitoring Relay

It is a multi-functional grid feeding monitoring relay, which provides interface protection and is to be installed between a renewable energy system and the public grid. This innovative relay guarantees grid stability and seeks to prevent blackouts.

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Description
Major Characteristics
  • A complete set of protection, related to the application;
  • 8 current input, 4 voltage input, 16 DI, 10 DO;
  • Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V;
  • 2 RS485 serial communication, IEC 60870-5-101, IEC60870-5-103 and Modbus-RTU;
  • 1 RS232 for user update;
  • 1 GPS for GPS timing;
  •  More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records;
  • Powerful graphic programmable Logic.
Panel Features
 

 

LCD Display

 

Dimension
  • Dimension
  • Cut-out Dimension 
Network Structure

 
Installation On-Site

 

Related Products
  • PZ72L-E4 Three phase Energy meter
  • ADF400L-EY Multi Channel Prepaid Energy Meter
  • APM830 Three Phase Power Quality Analyzer
  • AWT100-4G Wireless Communication Terminal 
  •  
  •  
  •  
Data Sheet
Main Parameters

 

Power Supply

Power supply: AC/DC220V,Or AC/DC110V,oR DC48V(Reference the wiring diagram)

Range: Power supply x (1±20%)

Maximum power consumption:≤10W(DC)

Rated Voltage

Rated Voltage:AC100V

Range:1-120V

Accuracy:±0.5%

Power Consumption:≤0.5VA(Single phase)

Overload capacity:1.2 times rated voltage for continous work;2 times for 10 seconds

Rated Current

Rated current: AC 5A/1A(See the device wiring diagram)

Range:0.04In~15In

Power consumption: ≤0.5VA(Single phase)

Over capacity:2 times rated current for continuous work;40 times for 1 second

Frequency

Rated frequency:50Hz or 60 Hz

Range:45~55Hz

Accuracy:±0.1Hz

Digital Inut

Rated Voltage: AC/DC220V,AC/DC110V,DC48V(Similar to power supply)

Voltage Range: Rated voltage x (1±20%)

Power Consumption:≤1W(DC220V)(Single channel)

Digital Output

Mechanical life:≥10000 times

Switching capacity:≥1000W,L/R=40ms

On current:continuous≥5A short time(200ms)≥30A

Interrupting capacity:≥30W,L/R=40ms

CONTACT US