ADL3000 is a smart meter designed for power supply system, industrial and mining enterprises and utilities to calculate the electricity consumption and manage the electric demand.
MINIMUM PACKAGE
|
||||
MINIMUM PACKAGE
|
Package Dimension(1 PC) 170*150*130mm |
Package Weight(1 PC) 0.372Kg |
||
WHOLE BOX PACKAGE
|
Package Dimension(36 PCS) 540*530*480mm |
Package Weight(36 PCS) 14.5kG |
||
PRODUCT HS CODE
|
9028301400 |
Function |
Function description |
Function provide |
Measurement of kWh |
Active kWh (positive and negative) |
■ |
Reactive kWh (positive and negative) |
■ |
|
A, B, C phase positive active kWh |
■ |
|
Measurement of electrical parameters |
U、I、P、Q、S、PF、F |
■ |
Measurement of |
2~31ST Voltage and current harmonic |
□ |
LCD Display |
8 bits section LCD display, background light |
■ |
Key programming |
4 keys to communication and set parameters |
■ |
Pulse output |
Active pulse output |
■ |
Reactive pulse output |
□ |
|
Clock pulse output |
□ |
|
Multi-tariff and functions |
Active switch input |
□ |
Switch output |
□ |
|
Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates |
□ |
|
Max demanded kWh and time happened |
□ |
|
Frozen data on last 48 months, last 90days |
□ |
|
Date, time |
□ |
|
Communication |
Infrared communication |
■ |
The first communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU |
□ |
|
The second communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU |
□ |
|
Temperature measurement |
Support 3 outlay NTC temperature |
□ |
“■” means standard, “□” means optional.
Specification |
3 phase 3 wires, 3 phase 4 wires |
|
Voltage |
Reference voltage |
3×100V、 3×380V、3×57.7/100V、 3×220/380V |
Consumption |
<10VA(Single phase) |
|
Impedance |
>2MΩ |
|
Accuracy class |
Error±0.2% |
|
Current |
Input current |
3×1(6)A (second connection with CTs’ cable already on site via external CTs of ADL3000-E/CT) 3×10(100)A (first connection with 3-phase load line via external CTs of ADL3000-E/CT)
|
Consumption |
<1VA(Single phase rated current) |
|
Accuracy class |
Error±0.2% |
|
Power |
Active, reactive, apparent power, error±0.5℅ |
|
Frequency |
45~65Hz, Error±0.2% |
|
Temperature |
-40℃~99℃ |
|
Energy |
Active energy (Accuracy class:0.5, 1), reactive energy(Accuracy class 2) |
|
Clock |
≤0.5s/d |
|
Energy pulse output |
1 active optocoupler output, 1 reactive optocoupler output |
|
Switching output |
1 Switching output |
|
Switching input |
1 optocoupler input |
|
Width of pulse |
80±20ms |
|
Pulse constant |
6400imp/kWh,400imp/kWh(Correspond with the basic current) |
|
Interface and communication |
RS485:Modbus RTU |
|
Range of communication address |
Modbus RTU:1~ 247; |
|
Baud rate |
1200bps~19200bps |
|
Relative temperature |
-25℃~+55℃ |
|
Relative humidity |
≤95℅(No condensation) |