ADF400L series multi-channel energy meter, through the way of combination module can realize largest 36 circuits single-phase or 12 circuits three-phase, CT connect or direct connect.
MINIMUM PACKAGE
|
||||
MINIMUM PACKAGE
|
Package Dimension(1 PC) 330*220*150mm |
Package Weight(1 PC) 1.45Kg |
||
WHOLE BOX PACKAGE
|
Package Dimension(36 PCS) 620*480*400mm |
Package Weight(36 PCS) 16kG |
||
PRODUCT HS CODE
|
9028301400 |
Parameter |
Description&Value |
|
Auxiliary Power Supply
|
Voltage |
3*220V/380V (for 3-phase sub modules); 220V AC (for 1-phase sub module) |
Power Consumption |
≤10W |
|
Input Voltage |
Rated Voltage |
3x 220/380V AC (3-phase); 220V AC(1-phase) |
Frequency |
50Hz |
|
Input Current |
Rated Current |
Max 80A Load Current (for 1-phase&3-phase sub module with direct connection); 3×1(6)A(for 3-phase sub module via CTs) |
Starting Current |
1‰ Ib (Class 0.5S) |
|
Accuracy |
Measurement |
Class 0.5 |
Clock |
≤0.5s/d |
|
Pulse |
Pulse Output |
1 Active Energy Pulse for each 3-phase Sub Module |
Pulse Width |
80ms±20ms |
|
Pulse Constant |
6400imp/kWh (3-phase) |
|
Communication |
RS485 |
MODBUS-RTU |
Infrared |
For Prepaid Card Scanning |
|
Ethernet |
MODBUS-TCP |
|
Environment |
Operating Temperature |
-20℃~+60℃ |
Storage Temperature |
-30℃~+70℃ |
|
Humidity |
≤95% (No condensation) |
|
Altitude |
<2000m |